For facility managers
Generator Service on a Schedule, With Records on File
Monthly, quarterly and annual visits for standby and emergency generators at businesses across Cheyenne and Northern Colorado, with outage windows planned around your hours and a written report after every visit.
Setting up a maintenance agreement
Walk-down and equipment list
It starts with a site visit. We record the generator’s make, model, kW rating, fuel type and engine hours, every transfer switch it feeds and what sits on each one, the controller, and any remote annunciator in the building. We also ask for whatever records exist and what your insurer, landlord or fire inspector has asked to see.
Pick the interval
The schedule depends on what the generator serves. A set that keeps an office’s phones and servers up during an outage is often well served by quarterly and annual visits. A set that feeds exit lighting, a fire pump or other life-safety loads usually needs monthly attention, because the standard that governs it says so. We write the schedule around whichever applies to your building.
Plan the outage windows
Transfer tests move real load. We set them for a time your operation can live with a short interruption on the transferred circuits, whether that means before opening, after close or a Sunday morning. Your staff knows the time and what to expect before our truck pulls in, and nobody in a back office gets surprised by the lights flickering.
A report after every visit
Each visit ends with a written report: readings, test results, run time, transfer timing, parts replaced, open deficiencies and what we recommend. You get a copy for the facility file. We keep one too, so trends show up across visits instead of hiding in a stack of loose service tickets.
Code and records
Which rules your generator falls under
Commercial generators are not all held to the same standard, and the difference changes how often yours needs attention and what paperwork you have to keep. The National Electrical Code splits standby power into three groups. Emergency systems under Article 700 power exit lighting and other life-safety loads. Legally required standby systems under Article 701 serve loads that a code or the local authority says must have backup. Optional standby under Article 702 covers everything else, from a restaurant’s walk-in coolers to a shop’s server closet.
For emergency and legally required systems, NFPA 110 usually sets the testing schedule where it has been adopted, including a monthly exercise under load, monthly operation of the transfer switch and a written log of both. Emergency systems also have to pick up their loads fast. The NEC allows an emergency system no more than 10 seconds, so we time the transfer on every test and write the number down. Optional standby systems have more freedom, though the manufacturer’s schedule and your insurer’s expectations still apply.
Isaac Garcia worked on power system upgrades at US federal facilities overseas before Moonlight Electric, where test records got read line by line. He holds state and city master licenses in Wyoming and Colorado, every electrician on our crew is licensed, and our apprentices train through an accredited program under that supervision.
What gets checked, and how often
Monthly
A visual inspection of the set, the enclosure and the fuel system. Battery voltage and charger output. Oil and coolant levels. A run under load for the time and minimum load the standard or the manufacturer calls for, and operation of the transfer switch. The log gets run time, voltage, frequency, oil pressure and coolant temperature.
Quarterly
The monthly list plus a closer look at belts, hoses, the block heater and the batteries themselves with a load or specific gravity test. We check the remote annunciator and the alarms, and look under the skid for fuel or coolant leaks that a monthly walk-by can miss.
Annually
Oil and filters, air filter and fuel filters, coolant testing or replacement on the manufacturer’s interval, and a full transfer switch inspection with the switch de-energized where the facility can allow it. Connections get tightened and checked for heat. We review the year’s logs, and if the monthly runs are not reaching the load the standard calls for, this is when we schedule a load bank test.
Transfer timing, every test
Every transfer test is timed from loss of utility to load on the generator, and from return of utility to load back on the normal source. A transfer that is getting slower points to a tired battery, a slow engine start or controller time delays that drifted or were set wrong at commissioning. Recording the number each time catches that trend early.
The parts that fail without warning
Most commercial generator failures we see during a real outage trace back to something that was sitting in plain sight for months. Three of them come up again and again.
Stored diesel
Diesel that sits in a tank for a year or more collects water and can grow sludge that plugs filters during the first long run. We check for water, look at the filters and tell you when the fuel should be tested or polished by a fuel service.
Coolant
Coolant has to handle a Wyoming winter and keep its corrosion inhibitors working. We test freeze protection, confirm the block heater draws current, and inspect hoses that bake all summer and freeze all winter.
Batteries and charger
Larger sets often crank on two batteries in series, and one weak cell drags the bank down. We load test the bank and check that the charger is neither starving nor cooking it.
Natural gas sets skip the stored-fuel problem, but we still watch how the engine handles a big load step, since bogging there can point to a gas supply that cannot keep up. Larger engines and process loads fall under our industrial generator work, and new installs or replacements go through our commercial backup generator service.
We maintain generators for businesses in Cheyenne, Laramie, Pine Bluffs and around Warren AFB, and in Northern Colorado from Fort Collins to Greeley. Have a standby unit at home too? Our home generator maintenance visit is a separate, simpler service. To get on the schedule, send us the generator details and we will set up the walk-down.
Facility manager questions
How often should a commercial generator be serviced?
It depends on what the generator serves. Sets feeding emergency or legally required loads usually need monthly testing and inspection under NFPA 110, plus a larger annual service. Optional standby sets kept for business continuity are often maintained quarterly and annually. We set the schedule after we see the equipment and the loads.
Do you keep the records an inspector or insurer will ask for?
Yes. Every visit ends with a written report covering readings, test results, run time, transfer timing, parts replaced and open deficiencies. You get a copy for your facility file, and we keep ours so the history is easy to pull when someone asks for it.
Will the business lose power during a test?
Only the circuits on the transfer switch, and only briefly while the switch transfers and returns. We schedule those tests with you ahead of time, usually before opening or after close. Monthly runs that do not move the transfer switch can often happen during business hours with no interruption at all.
Can you maintain a generator another company installed?
Yes. We service standby and emergency generators regardless of who installed them. The first visit includes a look at the install itself, the transfer equipment and the wiring, since problems there tend to show up later as generator problems.
What happens if you find a problem during a visit?
Small items like a loose connection or a worn belt we usually take care of during the same visit with your approval. Bigger repairs go into the report with a plain explanation of what failed and why it matters, and we schedule that work with you. A safety problem on an emergency system gets brought to you right away, before we leave the site.
Is load bank testing part of maintenance?
When the monthly runs are not reaching the load the standard or the manufacturer calls for, yes. A load bank test puts the generator under a controlled load for a set period and clears out the buildup that light loading leaves behind. We schedule it alongside the annual service when it is needed.
Put your generator on a schedule
Tell us what the generator serves and how it has been maintained so far. We will come walk it and lay out a schedule and reporting plan that fits your building.