When the generator sits there and does nothing

Home standby generators that will not start, start and never pick up the house, or flash a fault code the first cold night of the year. Isaac starts on the electrical side, because that is where most of these failures live.

Most dead generators have a small, findable problem

A standby generator that fails during an outage feels like a big, expensive problem. Usually it is not. The most common causes we find are a battery that could not crank in the cold, a charger that quit months ago, a tripped breaker on the generator, or a transfer switch that stopped talking to the controller. The engine itself is often fine.

The trouble is that a standby unit only gets a real test when the grid goes down, so problems hide for a long time. The weekly exercise run keeps the engine moving, but many units exercise without load, which means a bad transfer switch or a weak connection never shows up until the night you need it.

If the power is out right now and the generator will not cooperate, switch the controller to off before you reach into the enclosure, and leave the transfer switch cover closed. Either one can be live from the utility side or the generator side. Write down whatever the screen says, look to see whether the breaker on the generator has tripped, and then call.

Isaac Garcia is a master electrician licensed in Wyoming and Colorado. Before working in Cheyenne he worked on power system upgrades at US federal facilities overseas, where backup power was not optional. He works on the major home standby brands, including units somebody else installed. Call (307) 757-5553 from Cheyenne, Warren AFB housing, Laramie or Greeley, and tell him what the controller screen says.

Where we start

The first four things Isaac checks

1

The controller and its fault history

The controller logs what went wrong and when. Overcrank, low oil pressure, overspeed, under-voltage, low battery and similar codes each point to a different system, and the history shows whether this is the first failure or the fifth. We read it before touching anything else.

2

The battery and the charger

A standby battery that tests fine in September can fail to crank at ten below. We load test the battery and check that the charger is actually putting out voltage. A dead charger slowly drains the battery through the controller, and the generator fails the next time it tries to start.

3

Fuel, cold and the block heater

We confirm the gas valve is open and the supply pressure holds while the engine cranks. In winter we check the block heater and any battery warmer, since a cold engine with thick oil cranks slowly and may never fire. Snow drifted against the enclosure intake shows up here too.

4

The transfer switch

If the generator runs but the house stays dark, the switch is the suspect. We check the contactor or motor operator, the control relay, the sensing leads and the communication wiring between the switch and the generator, then force a transfer to watch it work.

Symptoms and what usually causes them

Large orange standby generator enclosure on a pad beside a gray building in Cheyenne, WY
Whatever the size of the enclosure, the same basic electrical faults account for most no-start and no-transfer calls.

It will not crank at all

Nothing happens when the controller calls for a start. Look first at the battery, the battery cables and terminals, the starter relay and the controller fuse. A controller left in the off position after the last service is more common than anyone likes to admit.

It cranks but will not run

The engine turns over and never catches, or starts and dies. Fuel supply, a failed fuel solenoid, fouled spark plugs, low oil shutting it down, or a speed sensor problem are the usual suspects. Cold weather makes every one of them worse.

It runs but will not transfer

The generator is humming and the house is still dark. That points at the transfer switch, the main line circuit breaker on the generator, or the wiring between the two. A tripped generator breaker after an overload is a quick fix. A burned contactor is a part replacement.

It transfers, then shuts down

The load came on and the generator could not hold it, or a sensor tripped it off. Overload from too much running at once, a load management module that is not shedding, and voltage or frequency faults all land here. We check the loads against the generator rating before blaming the engine.

It stopped exercising, or runs at odd hours

The weekly exercise depends on the controller clock and a healthy battery. After a long outage or a battery swap the clock can reset, so the unit runs at three in the morning or not at all. Some models also hold a fault until someone clears it, and they will not exercise again until then. We set the schedule and confirm the next run actually happens.

Wiring and breaker faults

Rodents chew wiring inside enclosures, terminals loosen with heat cycles, and breakers wear out. Loose connections show up as heat discoloration and intermittent faults. These are squarely electrical repairs, and they are the part of the job we handle every day.

What we fix, and when we send you elsewhere

We handle the electrical side of a generator from end to end: batteries, chargers, controllers, sensors, breakers, wiring, the block heater circuit and the transfer switch. We also take care of the common upkeep items that get a unit running again, such as spark plugs, oil and filters, air filters and fuel solenoids.

Internal engine repair is a different trade. If the problem turns out to be a failed engine, a scored cylinder or a major mechanical part, we will tell you what we found, show you how we found it, and point you to the right shop. You will not pay us to guess at an engine rebuild.

Once it runs, keep it running. A yearly generator maintenance visit catches the battery and charger problems behind most of these calls. If the switch itself is old or undersized, a new transfer switch installation may make more sense than repairing it. For the full picture of home standby systems, see our backup generator page, or send Isaac a message with the model number.

Generator repair questions

Why does my generator start in summer but fail in January?

Cold is hard on a standby battery and on engine oil. A battery that cranks fine at seventy degrees can lose much of its starting power below zero, and thick oil makes the engine turn over slowly. A failed block heater or battery warmer makes it worse. We load test the battery and check the cold-weather parts first.

My generator is running but the house has no power. What is wrong?

The power is not getting from the generator to the house. The usual causes are a tripped breaker on the generator, a transfer switch that did not change over, or a broken control or communication wire between the two. Do not try to force the switch by hand; call us and we will find the fault.

Do you repair generators you did not install?

Yes. A good share of our repair calls are on units installed by someone else, sometimes years ago. Isaac works on the major home standby brands and will tell you plainly if a particular part has to come from the manufacturer.

What does a fault code on my generator mean?

Each code points to a system: starting, fuel, oil pressure, speed, voltage or battery. The code alone does not always name the bad part, but it tells us where to look. Write down the code and any message on the screen before you reset anything, and tell us when you call.

How often should a standby generator battery be replaced?

Most standby batteries last a few years, and Cheyenne winters shorten that. Age matters less than test results, so we load test the battery on every visit and replace it when it falls short, not on a fixed calendar.

Can you repair the engine on my generator?

We handle the electrical systems and the common upkeep parts, such as spark plugs, filters, oil and fuel solenoids. Major internal engine repairs go to an engine shop, and we will tell you what we found before you decide anything.

Generator down?

Get the generator answering again

Tell Isaac the brand, the model and what the controller screen shows. He will tell you what he expects to find before he drives out.